On-load tap changers (OLTCs) are indispensable in regulating power transformers used in electrical energy networks and industrial applications. With over 50 years of experience, Easun MR is a leading player today in the tap changer market with over 80% market share. With a comprehensive range of on-load tap changers for nearly all network applications, Easun MR is the trusted partner to Utilities, Consultants and Transformer Industry in India
M TYPE
MODERN, SUPERIOR & VERSATILE
- Used in up to 765 kV Transformers
- Three-pole design for neutral application at 350A, 500A and 600A rating for three-phase wye-connected windings
- Single-pole design at 350A, 500A, 600A, 800A, 1200A, 1500A, 1800A, 2100A and 2400A ratings for auto connected windings or single-phase transformers
- Available with ±9, ±11, ±13, ±15, ±17 steps
- Special design available with 700 A, 3 Phase and 2100 and 2400 A, Single Phase
- Available on both star and delta-insulation to ground, and tap selector size can be selected independently of one another
- Convenient for bell-type tank installations
- Additional device for potential tie-in of tap winding, during change-over operation of the change-over selector
- High-speed transition resistor-type diverter switch with arc extinction at first current zero.
- Diverter switch uses sharp-action mechanics by energy accumulator mounted directly on diverter switch.
- Minimum possible tap selector dimension because four avilable sizes ensure matched inpulse voltage withstandability.
- Radial dimensions of the tap selector are reduced by special shaping of all parts on high potential. Distances between tap selector bars determined by actual voltage stress.
- Optimised integration of the change-over selector into the fine selector contact circle.
- Long life and reduced maintenance - rapid tap change operation. Low thermal stress on the transition resistors.
- Special contacts for alternative oil application.
- Simple tap selector design, effective contact cooling, high short-circuit withstandability.
Electrical parameters | ||||||||
TYPE | Current Rating (A) | Voltage Variants | BIL kV/kVp | Max. Rated Step Voltage (Volts) | Max. Operating Position | |||
Three Pole | Single Pole | Voltage Level (kV) | Vector | Linear | Pre-Selector | |||
M-Type | 350, 500, 600 & 700 | 350, 500, 600, 800, 1200, 1500, 1800, 2100 & 2400 | 72.5 | Y, D | 140/350 | 3300 | 22 | 35 |
123 | Y, D | 230/550 | ||||||
170 | Y | 325/750 | ||||||
245 | Y | 395/950 | ||||||
300 | Y | 460/1050 |
D TYPE
HEAVY DUTY & TIME TESTED
- Type ‘D’ Model is a true testimony of Easun-MR’s time tested credentials for superior tap changer technology. This model is in successful service since 1975 catering to normal network applications and to demanding heavy duty furnace applications.
- Current rating up to 500 A with 3-pole & up to 1500 A with 1 pole.
- Linear version applicable up to 18 position.
- Special design is available for 300 A.
- Voltage class up to 220 kV Class.
- Both star and delta applications are available.
- Maximum step voltage up to 2500 Volts.
- Separate diverter and selector model.
- Bi-directional power flow.
- Up to 35 positions available for pre-selector arrangements.
- Over 1500 in-tank installation in ultra heavy duty applications which involve 500 operations per day.
Electrical parameters | ||||||||
TYPE | Current Rating (A) | Voltage Variants | BIL kV/kVp | Max. Rated Step Voltage (Volts) | Max. Operating Position | |||
Three Pole | Single Pole | Voltage Level (kV) | Vector | Linear | Pre-Selector | |||
D-Type | 200, 400 & 500 | 200, 400, 600, 800, 1200 & 1500 | 36 | Y, D | 75/200 | 2500 | 18 | 35 |
60 | 140/350 | |||||||
110 | 230/550 | |||||||
150 | 325/750 |
V TYPE
COMPACT & ECONOMICAL
Electrical parameters | ||||||||
TYPE | Current Rating (A) | Voltage Variants | BIL kV/kVp | Max. Rated Step Voltage (Volts) | Max. Operating Position | |||
Three Pole | Single Pole | Voltage Level (kV) | Vector | Linear | Pre-Selector | |||
V-Type | 200, 350 & 500 | 350 & 700A | 40 | Y, D | 70/200 | 1500 | 14 & 18 | 27 |
76 | 140/350 | |||||||
123/76 | 230/550 |
OCTC
Electrical parameters of OCTC | ||||||||
TYPE | Current Rating (A) | Voltage Variants | BIL kV/kVp | Max. Rated Step Voltage (Volts) | Max. Operating Position | |||
Three Pole | Single Pole | Voltage Level (kV) | Vector | Linear | Pre-Selector | |||
OCTC | 350, 500 & 600 | 350, 500, 600, 800, 1000, 1200, 1500, 1800 & 2000 | 72.5 | Y, D | 140/325 | 6600 | 9 | NA |
123 | 230/550 | |||||||
170 | 325/750 | |||||||
245 | Y | 395/950 | ||||||
300 | 460/1050 |