ON LOAD TAP CHANGERS (OLTC) FOR POWER TRANSFORMERS

AMD
AMD
AMD
AMD

On-load tap changers (OLTCs) are indispensable in regulating power transformers used in electrical energy networks and industrial applications. With over 50 years of experience, Easun MR is a leading player today in the tap changer market with over 80% market share. With a comprehensive range of on-load tap changers for nearly all network applications, Easun MR is the trusted partner to Utilities, Consultants and Transformer Industry in India

M TYPE

MODERN, SUPERIOR & VERSATILE

  • Used in up to 765 kV Transformers
  • Three-pole design for neutral application at 350A, 500A and 600A rating for three-phase wye-connected windings
  • Single-pole design at 350A, 500A, 600A, 800A, 1200A, 1500A, 1800A, 2100A and 2400A ratings for auto connected windings or single-phase transformers
  • Available with ±9, ±11, ±13, ±15, ±17 steps
  • Special design available with 700 A, 3 Phase and 2100 and 2400 A, Single Phase
  • Available on both star and delta-insulation to ground, and tap selector size can be selected independently of one another
  • Convenient for bell-type tank installations
  • Additional device for potential tie-in of tap winding, during change-over operation of the change-over selector
  • High-speed transition resistor-type diverter switch with arc extinction at first current zero.
  • Diverter switch uses sharp-action mechanics by energy accumulator mounted directly on diverter switch.
  • Minimum possible tap selector dimension because four avilable sizes ensure matched inpulse voltage withstandability.
  • Radial dimensions of the tap selector are reduced by special shaping of all parts on high potential. Distances between tap selector bars determined by actual voltage stress.
  • Optimised integration of the change-over selector into the fine selector contact circle.
  • Long life and reduced maintenance - rapid tap change operation. Low thermal stress on the transition resistors.
  • Special contacts for alternative oil application.
  • Simple tap selector design, effective contact cooling, high short-circuit withstandability.
AMD
Electrical parameters
TYPE Current Rating (A) Voltage Variants BIL kV/kVp Max. Rated Step Voltage (Volts) Max. Operating Position
Three Pole Single Pole Voltage Level (kV) Vector Linear Pre-Selector
M-Type 350, 500, 600 & 700 350, 500, 600, 800, 1200, 1500, 1800, 2100 & 2400 72.5 Y, D 140/350 3300 22 35
123 Y, D 230/550
170 Y 325/750
245 Y 395/950
300 Y 460/1050

D TYPE

HEAVY DUTY & TIME TESTED

  • Type ‘D’ Model is a true testimony of Easun-MR’s time tested credentials for superior tap changer technology. This model is in successful service since 1975 catering to normal network applications and to demanding heavy duty furnace applications.
  • Current rating up to 500 A with 3-pole & up to 1500 A with 1 pole.
  • Linear version applicable up to 18 position.
  • Special design is available for 300 A.
  • Voltage class up to 220 kV Class.
  • Both star and delta applications are available.
  • Maximum step voltage up to 2500 Volts.
  • Separate diverter and selector model.
  • Bi-directional power flow.
  • Up to 35 positions available for pre-selector arrangements.
  • Over 1500 in-tank installation in ultra heavy duty applications which involve 500 operations per day.
AMD
Electrical parameters
TYPE Current Rating (A) Voltage Variants BIL kV/kVp Max. Rated Step Voltage (Volts) Max. Operating Position
Three Pole Single Pole Voltage Level (kV) Vector Linear Pre-Selector
D-Type 200, 400 & 500 200, 400, 600, 800, 1200 & 1500 36 Y, D 75/200 2500 18 35
60 140/350
110 230/550
150 325/750

V TYPE

COMPACT & ECONOMICAL

  • Current rating up to 500 A & Voltage up to 132 kV (Y/D).
  • Special designs are avilable for 250 and 400 A on request.
  • Both star and delta applications are available.
  • Step voltage is 1500 Volts.
  • In-built selector switch model.
  • Bi-directional power flow.
  • Very compact dimensional arrangement.
  • Easy removal of diverter switch inserts, making it maintenance friendly.
  • Linear version is avilable up to 14 positions.
  • Up to 27 positions are avilable with the pre-selector arrangement.
  • No barrier board problems.
  • AMD
    Electrical parameters
    TYPE Current Rating (A) Voltage Variants BIL kV/kVp Max. Rated Step Voltage (Volts) Max. Operating Position
    Three Pole Single Pole Voltage Level (kV) Vector Linear Pre-Selector
    V-Type 200, 350 & 500 350 & 700A 40 Y, D 70/200 1500 14 & 18 27
    76 140/350
    123/76 230/550

    OCTC

  • High speed snap action design.
  • Design occording IEC 60214-1.
  • Single and three phase Off-Circuit tap-changers for up to 4000 A rated through-current.
  • Rated insulation on level up to Vm=300kV is possible.
  • Higher values possible as special design.
  • High safty is ensured with special switching.
  • Compact, most roubst and state-of-the art design.
  • Modular concept, which allows to manufacture as per the required specification.
  • Optimized field design through smooth surface, soft edges and use of innovative materials.
  • Possible driveType: - Manual drive - Motor drive
  • Hands on Wheel
  • Easy Installation in the transformers
  • AMD
    Electrical parameters of OCTC
    TYPE Current Rating (A) Voltage Variants BIL kV/kVp Max. Rated Step Voltage (Volts) Max. Operating Position
    Three Pole Single Pole Voltage Level (kV) Vector Linear Pre-Selector
    OCTC 350, 500 & 600 350, 500, 600, 800, 1000, 1200, 1500, 1800 & 2000 72.5 Y, D 140/325 6600 9 NA
    123 230/550
    170 325/750
    245 Y 395/950
    300 460/1050